Description
Query about alarm status:
01 00 00 00 00 06 01 02 00 00 00 02
Response from the device:
In the case of a query about the status of inputs, the last 8 bits indicate the response range from 00 to FF. The values of the subsequent bits indicate the status of individual inputs.
Example:
01 00 00 00 00 04 01 02 01 00 – OK (normal status)
01 00 00 00 00 04 01 02 01 01 – Input 1 triggered
01 00 00 00 00 04 01 02 01 02 – Input 2 triggered
01 00 00 00 00 04 01 02 01 03 – Inputs 1 and 2 triggered
01 00 00 00 00 04 01 02 01 1A – Inputs 2, 4, and 5 triggered
TECHNICAL DATA
Power supply: | DC 8-28V |
Inputs/Ouputs: | 8DI, Ethernet, RS-485 |
Operating temperature: | -40°C ÷ +85°C |
Operating humidity: | 5% ~ 95%RH |
Transmission speed: | 9600bps (customizable) |
Connection mode: | TCP Slave |
Dimensions (without cable glands): | 121 x 72 x 34 mm |